Ordering designations: 3000-U41-XX, 3000-U42-XX
|
| Abstract | |||||||||
|
3000-U41-XX are electrical outlet units with a relay contact that switches mains power on/off for plugged devices. It is scheduled as an amplifier for relay contact outputs of ELM modules. 3000-U42-XX are similar, but in addition, sensors for observation of voltage and current of mains are contained. Actions are defined by assigning relay components or alarms and setting proper thresholds.
See also (information becomes more general downwards):
|
|||||||||
| Variants | |||||||||
|
Switched socket outlet; with connection cable intended for single wire connections to unencapsulated modules of housing version "KIT" (-00). Ordering designation: 3000-U41-00
|
||||||||
|
Switched socket outlet; with connection cable equipped with a specified plug for connecting encased modules of housing version "BOX" (-02) or 19 inch rack mount units. Ordering designation: 3000-U41-01
|
||||||||
|
Switched socket outlet with observation of mains voltage; with connection cables intended for single wire connections to unencapsulated modules of housing version "KIT" (-00). Ordering designation: 3000-U42-00
|
||||||||
|
Switched socket outlet with observation of mains voltage; with connection cables equipped with specified plugs for connecting encased modules of housing version "BOX" (-02) or 19 inch rack mount units.
Ordering designation: 3000-U42-01 |
||||||||
| Technical Data | |
| Switching range | 80...260V AC; 47...63Hz |
| Switching current | 10A |
|
Measuring range (3000-U42 only) |
80...260V AC; 47...63Hz |
|
Measuring output (3000-U42 only) |
1.67 ... 5.2V DC |
|
Cable length |
3 m |
| Recommended configuration of an ELM Sensor Component if connecting this sensor | |
| Parameter | Value |
|
Upper limit |
5200 (mV) |
|
Lower limit |
1670 (mV) |
|
Upper end of scale |
260 (V AC) |
|
Lower end of scale |
80 (V AC) |