Ordering designations: 3000-U25-XX
|
| Abstract | |||||||
|
This climatic sensor enables the measuring of the humidity and temperature in in-door- and out-door-area. It can be connected to Sensor Input Components of an ELM system. The power supply is done by the ELM system.
The climatic sensor is contained within a case with two mounting holes.
See also (information becomes more general downwards):
|
|||||||
| Variants | |||||||
|
Climatic sensor with connection cable intended for single wire connections to unencapsulated modules of housing version "KIT" (-00). Ordering designation: 3000-U25-00
|
||||||
|
Climatic sensor with connection cable equipped with a specified plug for connecting encased modules of housing version "BOX" (-02) or 19 inch rack mount units. Ordering designation: 3000-U25-01
|
||||||
| Technical data | ||
|
Humidity Sensor |
Measuring range |
0...100 % rel. humidity |
|
Accuracy |
±3.5 % (20...80 % r.h.); optional ±2 % (10...90 % r.h.) |
|
|
Response time |
≤4 sec |
|
|
Output |
0.5...5.5 V |
|
|
Measuring element |
capacitive, (dewing strength) |
|
|
Temperature sensor |
Measuring range |
-20...+80 °C |
|
Accuracy |
±0.5 K @ 25 °C |
|
|
Response time |
≤20 sec |
|
|
Output |
0.5...5.5 V |
|
|
Measuring element |
Semiconductor |
|
|
Operating voltage |
7.5...27 V DC |
|
|
Dimensions L x W x H |
65 x 31 x 22 mm |
|
|
Cable length |
2 m |
|
|
Current consumption |
approx. 0.8 mA |
|
|
Automatic self-test |
Becoming at sensor bugs the outputs switched on <10 mV |
|
|
Protection level - sensor |
IP 30 |
|
|
Protection level - electronic |
IP 65 |
|
|
Standards |
EMV and ESD checked EN 50082-1 and EN 50082-2 |
|
|
Operating conditions |
-20 to +80 °C
For the measuring least air speed needed row of RC crossways to the sensor 0.3 m/s |
|
|
Connector/Cable |
||
|
Signal |
Pin number of Plug (U25-01 only) | Wire Color |
| 12 VDC | 1 | Red |
| Temperature sensor | 2 | Green |
| Ground | 3 | Blue |
| Humidity sensor | 4 | Yellow |
![]() |
||
| Recommended configuration of an ELM Sensor Component if connecting this sensor | ||
| Sensor | Parameter | Value |
| Temperature |
Upper limit |
5500 (mV) |
|
Lower limit |
500 (mV) |
|
|
Upper end of scale |
80 (°C) / 176 (°F) |
|
|
Lower end of scale |
-20 (°C) / -4 (°F) |
|
| Humidity |
Upper limit |
5500 (mV) |
|
Lower limit |
500 (mV) |
|
|
Upper end of scale |
100 (%) |
|
|
Lower end of scale |
0 (%) |
|