Ordering designations: 3000-U38-XX
|
| Abstract | |||||||
|
This sensor is used to detect vibration, vandalism, destruction and theft. It measures acceleration along one axis. The sensor can be connected to a Sensor Input Component of an ELM system. Actions are defined by assigning relay components or alarms and setting proper thresholds. The power supply is done by the ELM system.
The sensor is contained within a case with two mounting holes.
See also (information becomes more general downwards):
|
|||||||
| Variants | |||||||
|
Acceleration/Tilt sensor with connection cable intended for single wire connections to unencapsulated modules of housing version "KIT" (-00). Ordering designation: 3000-U38-00
|
||||||
|
Acceleration/Tilt sensor with connection cable equipped with a specified plug for connecting encased modules of housing version "BOX" (-02) or 19 inch rack mount units. Ordering designation: 3000-U38-01
|
||||||
| Technical Data | |
|
Measuring range |
+/-5 g |
|
Measuring axis |
Z-axis |
|
Output at 0 g |
2.5V +/-0.25V |
| Sensitiveness | (0.4 +/-0.02) V/g |
| Non-linearity | +/-1% FSO |
| Bandwidth | 50 Hz |
| Protection against overload | up till 1500 g |
| Measuring element | capacitive |
|
Operating voltage |
7.5...15V DC |
| Current consumption | approx. 2 mA |
| Operating conditions | -40...+70 °C |
| Protection level | IP 65 |
| Standards | EMV and ESD checked EN 50082-1 and EN 50082-2 |
|
Dimensions L x W x H |
65 x 31 x 22 mm |
|
Cable length |
2 m |
|
Connector/Cable |
||
|
Signal |
Pin number of Plug (U38-01 only) | Wire Color |
| 12 VDC | 1 | Red |
| Sensor | 2 | Green |
| Ground | 3 | Blue |
| (not used) | 4 | - |
![]() |
||
| Recommended configuration of an ELM Sensor Component if connecting this sensor | |
| Parameter | Value |
|
Upper limit |
4500 (mV) |
|
Lower limit |
500 (mV) |
|
Upper end of scale |
5 (g) |
|
Lower end of scale |
-5 (g) |
| Set points |
Recommendations: Both set points should be set very close to the normal value given by the sensor. Usually an alarm line should be assigned to both set points. The latch mode should be used for the alarm. |